The Mixvent Series is a very compact design of mixed-flow fans that is part of a very flexible system designed specifically for use in homes, hotels and apartments etc., as well as for hot and cold air transfer from one room to another.
Construction
The casings of the 1300/250 and 2000/315 models are of epoxy coated steel; other sizes are of reinforced injection moulded plastic.
All units are provided with an integral mounting foot. Impellers are of injection moulded plastic/steel and of mixed-flow design.
Motors
Type - 2-speed. Models 160-350 are shaded pole; 500 and above are squirrel cage induction motor.
Bearings - sleeve up to size 350/125 and ball for all other models.
Speed-controllable using VA type speed controller in high speed only.
Internal Thermal Protection
By fuse to size 350/125 and auto-reset for the remainder.
Testing
Air flow to BS848:Part 1, 1980 Noise to BS848:Part 2, 1985
Special Features
The fans can be removed without disturbing the connecting ductwork via specially designed support brackets and a 2-speed switch can be supplied that suits all models.
In addition to being used as single-stage fans the Mixvent range can be arranged in parallel, in series or in both parallel and series.
Such flexibility enables higher air flow and pressure demands to be met. Refer to AMS representative for details.
Dimensions
Model TD
A
B
C
D
E
FØ
GØ
160/100
82
51
96
47
232
97
137
250/100
100
60
115
80
303
97
176
350/125
100
60
115
80
258
123
176
500/150
112
60
127
80
295
147
200
800/200
124
94
141
100
302
198
217
1000/250
155
145
192
145
386
248
272
1300/250
155
145
192
145
386
248
272
2000/315
181
182
224
182
450
312
336
Model TD
A
B
C
D
EØ
FØ
G
H
I
J
KØ
4000/355
377
238
451
224
426
354
160
368
474
340
8.5
6000/400
407
249
492
267
487
399
160
425
547
370
8.5
Technical Data
Model TD
r.p.m.
dB(A) @3m
Watts
1 ph Amps
m3/hr
Max amb °C
Kg
160/100
2520/2220
29/26
35/16
0.16/0.10
180
40
1.4
250/100
1860/1500
42/33
40/25
0.26/0.18
240
40
2.0
350/125
2220/1920
43/40
50/30
0.37/0.26
360
40
2.0
500/150
2520/1860
47/39
68/45
0.30/0.22
580
60
2.7
800/200
2520/1860
43/45
140/100
0.60/0.53
1100
60
4.9
1000/250
2520/2100
49/43
155/85
0.65/0.39
1010
60
9.4
1300/250
2520/1980
57/51
180/140
0.72/0.48
1300
60
9.4
2000/315
2760/2520
59/57
260/160
1.30/0.90
2000
60
14
Duty free
Sound Pressure level
Max operating
Max Power
Max
discharge
(dB(A))@1.5m
Model TD
r.p.m.
absorbed W
current A
(m3/hr)
Inlet
Outlet
Rad
temperature °C
Kg
4000/355
1400
345
1.53
3760
61
63
50
40
19
6000/400
1400
665
2.97
5420
65
67
51
40
26
Permormance
Q = Air volume in m3/hr and m3/s
Pe = Static pressure in mm WG and Pa
Dry air at 20ºC and 760mmHg.
Air flow data in accordance with the following standards: UNE 100-212-89, BS 848 Part 1, AMCA 210-85, AsSHRAE 51-1985
HS = High Speed MS = Medium Speed LS = Low Speed
Suggested Specifications
The In-line fans shall be of the Mixvent Series as supplied by AMS.
Impellers shall be of mixed flow design and driven by 2-speed single-phase motors with integral thermal protection.
The Mini Centrifugal Roof Fan series are the new type roof extract units available in 2 sizes and suitable for vertical and horizontal installation. The low noise external motor and high efficient backward bladed impeller meets the requirement of efficient ventilation in residential, commercial and light industrial applications.
The Decor Series can be wall or ceiling mounted and is designed to exhaust stale and moist air from bathrooms, toilets, laundries etc. They are also suitable for ventilating all types of small or closed areas.
The Silent Series is a low profile mixed-flow in-line fan that produces low noise when in operation.
It does this through a specifically designed perforated internal skin that directs sound waves produced inside the fan to a layer of sound absorbent material.
The low-profile TD-EVO 250 and 315 in-line mixed-flow fans for circular ducts have a unique design where the support bracket allows the motor and impeller assembly to be fitted or removed without dismantling the adjacent ducting.