Square plate axial fans |
Features
|
- The Compact 2000 Series of square plate axial fans can be mounted in any position.
- They are a high quality product suitable for a wide range of applications.
|
Construction
|
- Galvanised steel construction with a high quality polyester epoxy finish as standard.
- Impellers have GRP blades as standard; aluminium blades are an optional extra.
|
Motors
|
- Type - squirrel cage induction motor.
- Sizes 710 and 800 can be fitted with motors to suit virtually any specification.
- Electricity supply - 220-240V, single or 415V, three-phase, 50Hz.
- Bearings - sealed-for-life, ball.
- Speed-controllable using electronic, auto-transformer or inverter controllers.
- Weatherproof to IP55.
- Operating temperature range -20ºC to +70ºC. Maximum ambient when being speed-controlled is 40ºC.
|
Internal Thermal Protection
|
- Manual-reset protection is supplied as standard up to size 630; they are an optional extra on size 710.
|
Testing
|
- Air flow tests to BS848:Part 1, 1980.
- Noise tests to BS848:Part 2, 1985.
|
Special Features
|
- Can be mounted at any angle.
- A full guard is fitted as standard to 025. to 710. units only.
- A flying lead is fitted as standard with Ø20 flexible conduit to 025. to 063. units only.
- Derate the performance by at least 25% if air flow direction is reverse to standard.
|
Dimensions
|
|
|
Model SCP |
AØ |
BØ |
C |
D |
E |
F |
G |
HØ |
Kg |
250 |
250 |
260 |
370 |
320 |
100 |
85 |
10 |
7 |
7 |
315 |
325 |
330 |
430 |
380 |
95 |
85 |
10 |
10 |
10 |
350 |
360 |
370 |
485 |
435 |
95 |
85 |
10 |
10 |
10 |
400 |
410 |
420 |
540 |
490 |
95 |
95 |
12 |
10 |
15 |
450 |
460 |
470 |
575 |
535 |
95 |
95 |
12 |
10 |
17 |
500 |
510 |
535 |
655 |
615 |
145 |
100 |
15 |
10 |
24 |
560 |
575 |
600 |
725 |
670 |
145 |
100 |
15 |
10 |
27 |
630 |
645 |
670 |
805 |
750 |
140 |
105 |
20 |
10 |
34 |
710 |
716 |
760 |
850 |
810 |
* |
98 |
27 |
14 |
37/61 |
|
Technical Data
|
|
|
|
|
|
|
|
|
Max. |
In-duct Sound Power Levels |
|
|
dB(A) |
1 ph. |
|
3 ph. |
|
|
amb |
LwdB re 1pW |
Model SCP |
rev/s |
@3m |
kW |
Amps* |
Frame*** |
kW |
Amps* |
°C |
63 |
125 |
250 |
500 |
1k |
2k |
4k |
8k |
250-4 |
23 |
42 |
0.09 |
0.90 |
- |
0.12 |
0.50 |
70◊ |
66 |
64 |
61 |
60 |
56 |
55 |
51 |
45 |
315-4 |
23 |
45 |
0.09 |
0.90 |
- |
0.12 |
0.50 |
70◊ |
69 |
67 |
63 |
63 |
60 |
57 |
53 |
49 |
350-4 |
23 |
49 |
0.09 |
0.90 |
- |
0.12 |
0.90 |
70◊ |
71 |
70 |
65 |
67 |
66 |
59 |
55 |
54 |
400-4 |
23 |
52 |
0.25 |
1.80 |
- |
0.37 |
1.40 |
70◊ |
71 |
72 |
68 |
70 |
69 |
64 |
61 |
56 |
400-6 |
15 |
44 |
0.12 |
1.05 |
- |
0.16 |
0.93 |
70◊ |
67 |
63 |
66 |
63 |
61 |
53 |
48 |
43 |
450-4 |
23 |
54 |
0.25 |
1.80 |
- |
0.37 |
1.40 |
70◊ |
74 |
75 |
72 |
71 |
70 |
67 |
64 |
56 |
450-6 |
14 |
46 |
0.12 |
1.05 |
- |
0.18 |
0.68 |
70◊ |
66 |
64 |
66 |
64 |
61 |
58 |
54 |
45 |
500-4 |
23 |
58 |
0.55 |
3.60 |
- |
0.55 |
1.75 |
70◊ |
77 |
81 |
78 |
73 |
72 |
72 |
69 |
62 |
500-6 |
14 |
51 |
0.18 |
1.55 |
- |
0.25 |
0.94 |
70◊ |
72 |
67 |
69 |
68 |
69 |
63 |
57 |
51 |
560-4 |
23 |
62 |
0.75 |
4.90 |
- |
0.75 |
2.00 |
70◊ |
81 |
83 |
80 |
79 |
78 |
75 |
73 |
67 |
560-6 |
14 |
57 |
0.25 |
2.20 |
- |
0.25 |
0.94 |
70◊ |
76 |
73 |
76 |
76 |
73 |
71 |
60 |
56 |
630-4 |
23 |
66 |
1.1 |
7.88 |
- |
1.50 |
4.30 |
70◊ |
81 |
82 |
86 |
84 |
80 |
78 |
77 |
72 |
630-6 |
14 |
60 |
0.55 |
6.00 |
- |
0.55 |
2.00 |
70◊ |
83 |
80 |
78 |
77 |
76 |
73 |
68 |
59 |
714/1 |
23 |
67 |
- |
- |
D100L |
2.20 |
4.60 |
40◊ |
90 |
80 |
84 |
3 |
3 |
82 |
81 |
76 |
714/2 |
23 |
71 |
- |
- |
D100L |
3.00 |
6.20 |
40◊ |
88 |
85 |
88 |
88 |
87 |
85 |
85 |
76 |
714/3 |
23 |
71 |
- |
- |
D112M |
4.00 |
8.00 |
40◊ |
91 |
90 |
93 |
91 |
87 |
86 |
83 |
77 |
716/1 |
16 |
62 |
- |
- |
D09S |
0.75 |
2.20 |
40◊ |
85 |
79 |
77 |
79 |
83 |
78 |
73 |
71 |
716/2 |
16 |
63 |
- |
- |
D09L |
1.10 |
3.00 |
40◊ |
4 |
81 |
82 |
83 |
78 |
73 |
72 |
61 |
716/3 |
16 |
68 |
- |
- |
D100L |
1.50 |
3.60 |
40◊ |
0 |
84 |
85 |
89 |
86 |
79 |
72 |
68 |
|
|
*Amperages shown are a guide only. Refer to our Sales Department for accurate figures at time of order.
** Use auto-transformer control only
***Use inverter control only
◊ Maximum ambient if 50°C when being speed controlled.
The in-duct Sound Power Levels are for the Outlet Side of the fan; Inlet Side values are generally 1-2 dB lower. The levels are based on the fans operating at approx. 50% of peak pressure.
|
Suggested Specifications
|
- The Compact 2000 Series of plate mounted axial fans shall be as supplied by AMS.
- The axial impellers shall be of GRP and fitted with Tech-Lock bushes for easy removal and fitting.
- Square plates shall be of galvanised construction with a polyester epoxy finish.
- All models shall be fully tested to BS848:Part 1, 1980 for air flow to BS848:Part 2, 1985 for noise.
|
Performance
|
|
Ancillaries
|
|
Auto Cad
|
|
|
|
SCP 250
|
SCP 315
|
SCP 350
|
SCP 400
|
SCP 500
|
|
|
|
|
|
SCP 560
|
SCP 630
|
SCP 710
|
|
PDF
|
|
|
|
|
|
|
|
|
|
|