Features
|
- The HIT Series of duct mounted centrifugal in-line fans is suited to a wide range of residential, commercial and industrial exhaust or supply air applications, such as toilets, kitchens, bathrooms, offices, restaurants and equipment cooling.
- All models are designed for direct connection to standard diameter circular ducting and come standard with manufacturing.
|
Construction
|
- Corrosion resistant pressed galvanised sheet steel body with backward-curved centrifugal impeller.
- Electrical terminal on flying lead.
|
Motor
|
- Type - external rotor, squirrel cage induction motor. Electrical supply
- - 220-240V, single-phase, 50Hz.
- - 60Hz available upon request. Bearings - sealed for life, ball.
- Speed - controllable with 2-speed switch available for Hi/Lo speed operation.
- Motor - IP44 Protection.
|
- Testing Air flow testing to BS848: Part 1,1980, ACMA 210-85 and ASHRAE51-1985.
|
Internal Thermal Protection
|
- Auto-reset thermal protection is supplied as standard on all units.
|
Special Features
|
- Can be mounted on any angle.
- Suitable for ducting on intake and/or discharge side and for supply or exhaust applications.
|
Dimensions
|
|
|
|
Model HIT |
A |
B |
C |
D |
E |
F |
G |
Kg |
100 |
98 |
205 |
130 |
236 |
284 |
270 |
47 |
3.7 |
125 |
123 |
193 |
130 |
236 |
284 |
270 |
47 |
3.7 |
150 |
148 |
195 |
165 |
278 |
326 |
312 |
47 |
3.6 |
200 |
198 |
235 |
190 |
333 |
392 |
372 |
100 |
5.5 |
250B |
248 |
210 |
190 |
333 |
392 |
372 |
100 |
5.3 |
315B |
313 |
265 |
227 |
400 |
460 |
440 |
100 |
8.8 |
|
Performance
|
|
|
Technical Data
|
|
In-duct Sound Power Levels LwdB re 1pW |
|
|
|
dBA |
1ph |
|
|
Model HIT
|
63 |
125 |
250 |
500 |
1K |
2K |
4K |
8K |
m3/hr |
A |
r.p.s. |
@3m |
W |
kW |
Kg |
100 L |
56 |
56 |
62 |
59 |
59 |
54 |
47 |
42 |
158 |
0.3 |
33 |
42 |
70 |
0.05 |
3 |
100 M |
54 |
58 |
64 |
61 |
61 |
57 |
50 |
45 |
194 |
0.3 |
38 |
44 |
70 |
0.05 |
3 |
100 H |
57 |
60 |
67 |
63 |
63 |
59 |
52 |
47 |
219 |
0.3 |
43 |
46 |
70 |
0.06 |
3 |
125 L |
56 |
54 |
57 |
55 |
54 |
51 |
46 |
43 |
212 |
0.3 |
28 |
37 |
70 |
0.05 |
3 |
125 M |
57 |
58 |
63 |
60 |
60 |
57 |
51 |
43 |
277 |
0.3 |
36 |
43 |
70 |
0.05 |
3 |
125 H |
60 |
60 |
66 |
63 |
63 |
60 |
55 |
48 |
342 |
0.3 |
41 |
47 |
70 |
0.06 |
3 |
150 L |
56 |
54 |
57 |
55 |
54 |
51 |
46 |
43 |
324 |
0.51 |
30 |
37 |
110 |
0.05 |
5 |
150 M |
57 |
58 |
63 |
60 |
60 |
57 |
51 |
43 |
403 |
0.51 |
36 |
43 |
110 |
0.05 |
5 |
150 H |
60 |
60 |
66 |
63 |
63 |
60 |
55 |
48 |
464 |
0.51 |
43 |
47 |
110 |
0.06 |
5 |
200 L |
56 |
61 |
63 |
58 |
58 |
56 |
46 |
37 |
680 |
0.63 |
28 |
42 |
140 |
0.13 |
5 |
200 M |
57 |
66 |
66 |
63 |
63 |
61 |
55 |
48 |
792 |
0.63 |
33 |
47 |
140 |
0.14 |
5 |
200 H |
59 |
64 |
69 |
67 |
67 |
66 |
60 |
55 |
914 |
0.63 |
41 |
51 |
140 |
0.16 |
5 |
250B L |
59 |
61 |
58 |
57 |
58 |
55 |
45 |
35 |
680 |
0.65 |
20 |
41 |
145 |
0.13 |
6 |
250B M |
60 |
68 |
62 |
63 |
63 |
61 |
55 |
43 |
867 |
0.65 |
33 |
46 |
145 |
0.14 |
6 |
250B H |
65 |
64 |
65 |
68 |
68 |
65 |
63 |
55 |
1119 |
0.65 |
41 |
52 |
145 |
0.16 |
6 |
315B L |
67 |
75 |
66 |
68 |
67 |
66 |
61 |
62 |
1616 |
1.07 |
35 |
51 |
240 |
0.21 |
8 |
315B M |
68 |
76 |
67 |
71 |
69 |
67 |
64 |
64 |
1746 |
1.07 |
38 |
53 |
240 |
0.22 |
8 |
315B H |
69 |
70 |
68 |
74 |
71 |
69 |
65 |
65 |
1861 |
1.07
|
41 |
56 |
240 |
0.23 |
8 |
|
Suggested Specifications
|
- In-line fans of the HIT Series shall be as supplied by AMS.
- Impellers shall be backward-curved centrifugal design and driven by speed-controllable external rotor motors with integral thermal overload protection.
- The housing is of pressed galvanised steel.
|
Wiring
|
|
Ancillaries
|
|
Auto Cad
|
|
HIT 100 |
HIT 125 |
HIT 150 |
HIT 200 |
|
|
|
|
HIT 250
|
HIT 315
|
|
PDF
|
|
|
|
|
|
|
|
|