Features
|
- The Mixvent-TH range of mixed flow roof fans are available in four nominal model sizes with performance ranges from 355 up to 1725 m³/hr. The products are supplied as standard for extract operation.
- However, the motor and impeller casing can be removed and turned through 180° to provide supply air ventilation.
- All models incorporate single phase two speed motors as standard.
- All motors used within the Mixvent-TH range are also suitable for speed control using electronic or auto-transformer speed control regulators.
|
Construction
|
- The Mixvent-TH models 500 and 800 are manufactured from high strength injection moulded plastic, and models 1300 and 2000 from high grade pressed sheet steel.
- The base and cowl assembly are manufactured from sheet steel.
- All models incorporate a bird guard and base cable gland entry point as standard.
- All metallic parts are protected with a black epoxy-polyester weatherproof paint coating.
|
Motors
|
- All models incorporate single external rotor motors with two speeds connections which are also suitable for speed control using voltage regulators. The following standard specifications apply:
- 230V 50Hz - Class B insulation - IP44 protection - Auto-Reset Thermal Overload Protection - Sealed for life, ball bearing assemblies |
Dimensions
|
|
|
Model TH |
A |
B |
C |
D |
E |
F |
G |
H |
I |
500 |
400 |
349 |
300 |
150 |
245 |
10 |
20 |
274 |
33 |
800 |
400 |
371 |
300 |
198 |
245 |
10 |
20 |
306 |
36 |
1300 |
546 |
457 |
435 |
248 |
330 |
12 |
20 |
372 |
42 |
2000 |
735 |
544 |
560 |
312 |
450 |
12 |
20 |
450 |
50 |
|
Technical Data
|
- The Mixvent-TH is a roof mounted mixed flow extract or supply air fan designed for direct connection to circular ducting.
- It has a two-speed motor, also suitable for speed control.
- It is suitable for extract/supply air temperatures up to +60°C (140°F).
- All models include a weatherproof anticorrosive epoxy polyester paint finish.
- Fan/impeller can be removed without dismantling the ductwork or base.
- Spigot flange connections facilitate installation.
|
Model TH |
|
r.p.m. |
|
W |
|
A |
|
m3/hr |
|
°C |
dB(A) |
kg |
|
|
Speed |
|
Speed |
|
Spped |
|
Speed |
|
|
|
|
|
|
H |
L |
H |
L |
H |
L |
H |
L |
|
|
|
500/150 |
Extract |
2450 |
1800 |
68 |
40 |
0.26 |
0.19 |
470 |
355 |
60 |
49.5 |
3.8 |
Supply |
2450 |
1800 |
67 |
40 |
0.25 |
0.19 |
505 |
380 |
45 |
500/160 |
Extract |
2450 |
1800 |
68 |
40 |
0.26 |
0.19 |
470 |
355 |
60 |
49.5 |
3.8 |
Supply |
2450 |
1800 |
67 |
40 |
0.25 |
0.19 |
505 |
380 |
45 |
800 |
Extract |
2500 |
2100 |
140 |
118 |
0.58 |
0.52 |
775 |
620 |
60 |
53 |
5.6 |
Supply |
2500 |
2000 |
140 |
118 |
0.58 |
0.52 |
860 |
695 |
52 |
1300 |
Extract |
2400 |
1800 |
170 |
120 |
0.83 |
0.52 |
1100 |
780 |
60 |
59.5 |
11.2 |
Supply |
2400 |
1800 |
172 |
110 |
0.76 |
0.49 |
1150 |
845 |
58.5 |
2000 |
Extract |
2480 |
1750 |
255 |
160 |
1.27 |
0.79 |
1200 |
60 |
60 |
67 |
17.2 |
Supply |
2480 |
1800 |
300 |
190 |
1.27 |
0.79 |
1245 |
60 |
63.5 |
|
Performance
|
|
Sound Data
|
|
The values of the sound levels given in the tchnical charactgeristic chart are sound pressure olevels measured in dB(A) at a distance of 3m with the maximum airflow.
To obtain the sound power level at A or B, for extract operation, add to the sound pressure level (SPLExtract) given in the Technical Data chart, the correction value shown in the following table.
|
|
|
Frequency band Hz |
Model TH |
|
125 |
250 |
500 |
1000 |
2000 |
4000 |
8000 |
500 |
A |
-7.5 |
-3 |
9 |
6 |
11 |
4 |
-2 |
B |
-7.5 |
6 |
13.5 |
17.5 |
14.5 |
4.5 |
-3 |
800 |
A |
-7.5 |
3.5 |
8 |
9.5 |
14 |
9 |
0 |
B |
-4 |
7.5 |
15 |
16 |
14.5 |
9 |
1.5 |
1300 |
A |
-13.5 |
0 |
1 |
12 |
9 |
4 |
0 |
B |
-11 |
5.5 |
11.5 |
17.5 |
15 |
7 |
-0.5 |
2000 |
A |
-21.5 |
-7 |
-3 |
7 |
5.5 |
-2 |
-8.5 |
B |
-16.5 |
2.5 |
7 |
20 |
7.5 |
1 |
-8 |
|
AUTO CAD
|
|
|
TH 500 |
TH 800 |
TH 1300 |
TH 2000 |
|
|
|
|
|
|
|
PDF
|
|
|
|
|
|
|
|
|