JV Axial Jet Fans for Car Parks

  Features

  • The JV Series of axial jet-induction fans can meet various customer requirements for car park ventilation.
  • The 315 and 400mm diameter and 24 model variants provide options for Uni-directional or Truly-reversible airflow, ambient or high temperature rating and single or dual speed.

  Construction

  • Galvanised steel housing with integral aerodynamically designed silencers.
  • With the integral 4-Point mounting feet, the unit can be easily mounted to the ceiling.

  Impellers

  • Adjustable pitch aerofoil section impellers are provided with high quality pressure die cast aluminium alloy (LM6) blades.
  • The blades are positively locked by pinning, providing added security for operation in the smoke regime.
  • Impellers are dynamically balanced to Grade G6.3. Hubs are made from pressure die cast aluminium (LM24).

  Motors

  • Motors are totally enclosed and airstream cooled, metric frame protested to IP55.
  • Motors have Class F or H insulation and are rated for normal continuous duty and a once only emergency operation in smoke conditions of 200OC or 300OC for 2 hours.
  • Motors are either single or 2-speed, the 2-speed with a Dahlander winding with direct starting at both speeds.

Testing

  • Thrust-air performance based on tests to BS848 Part 10, 1999 “Fans for general purpose - Performance testing of jet fans”.
  • Noise data based on tests to BS848:Part 2, 1985.
  • High temperature requirements tested to AS4429:1999 All JetVent units are tested at elevated temperatures in accordance with the requirements of the European standard EN 12101 - 3:2002.

  Dimensions

 
  Dimensions, mm  
Model JVU/R A B C D E F G (Max) Kg
CPA-315 250 300 315 265 447 9 1751/1876(R) 51/72(R)
CPA-400 339 400 400 350 523 9 2323/2440(R) 72/73(R)

  Technical Data

Fan Free In-duct Sound Power Levels
Speed Air Thrust JV ..3ph Max dB(A) Speed LwdB re 1pW
Model JV/JVS r/s m3/s N kW Amps  °C @ 3m Settieng 63 125 250 500 1k 2k 4k 8k
U-CPA-315-2-3 48 0.96 20 0.55 1.35 40* 59 - 73 79  86  77  70  65  64  60 
U-CPA-315-4-3 24 0.48 5 0.55 1.4 40* 49 - 61  72  66  68  63  61  57  52 
U-CPA-315-2/4-3 48 0.96 20 0.8 1.9 40* 59

High

73  79  86  77  70  65  64  60 
24 0.48 5 0.16 0.4 40* 49 Low 61  72  66  68  63  61  57  52 
U-CPA-400-2-3 48 1.95 50 1.5 2.9 40* 62 - 86  81  88  79  70  69  70  68 
U-CPA-400-4-3 24 0.97 12 1.1 2.6 40* 47 - 72  80  69  63  55  54  55  49 
U-CPA-400-2/4-3 48 1.95 50 1.7 3.5 40* 62 High 86  81  88  79  70  69  70  68 
24 0.97 12 0.34 0.8 40* 47 Low 72  80  69  63  55  54  55  49 
R-CPA-315-2-3 48 0.97 20 0.55 1.35 40*

61

 - 73  82  87  79  74  69  67  64 
R-CPA-315-4-3 24 0.49 5 0.55 1.4 40* 50 61  71  68  72  62  60  57  52 
R-CPA-315-2/4-3 48 0.97 20 0.8 1.9 40* 61 High  73  82  87  79  74  69  67  64 
24 0.49 5 0.16 0.4 40* 50 Low  61  71  68  72  62  60  57  52 
R-CPA-400-2-3 48 1.99 50 1.5 2.9 40* 63 88  83  89  80  73  73  74  70 
R-CPA-400-4-3 24 1.00 12 1.1 2.6 40* 54 73  89  72  70  58  56  55  53 
R-CPA-400-2/4-3 48 1.99 50 1.7 3.5 40* 63 High  88  83  89  80  73  73  74  70 
24 1.00 12 0.34 0.8 40* 54 Low  73  89  72  70  58  56  55  53 
* Smoke-Spill model can operate at 300°C for 2 hours and has an ambient maximum temperature of 70°C.

  Suggested Specifications

  • The JetVent Axial Jet-induction fans shall be of the JetVent JV series as supplied by AMS and be of the model number shown.

  PDF