Features
|
- The Compact ‘PowerPlus’ is specifically developed for high pressure requirements with the Contra-Rotating design that ensures higher performance without increased noise levels and operating costs.
- The Compact ‘PowerPlus’ comprises three standard sizes - 500, 560 and 630mm diameter - with a duty range of between 1,8 to 4,3 m3/sec and provide static pressures of up to 600 Pa.
- The units are suitable for external mounting.
|
Applications
|
- Areas that are not suited to single stage fans, especially commercial kitchens with higher working temperatures and regulations for greater efficiency in kitchen filtration systems.
- The Compact ‘PowerPlus is suited for operation in up to 95% relative humidity.
|
Construction
|
- The all metal fan casing provides a long lasting and robust construction with the units being constructed from a single sheet of steel.
- Both motors and axial impellers are mounted within the length of the unit casing.
- The fan casing is hot dipped galvanised after fabrication.
- A single terminal IP55 box is mounted on the outside of the casing that ensures easier and faster wiring.
|
Motors
|
- Motors are lightweight induction motors with sealed for life, maintenance free ball bearings, which allows the fan to be installed at any angle.
- Each motor is matched to the aerodynamic performance of the impeller.
- Motors are Class F insulated to EN 60034-5, weatherproofed to IP55 and all suitable for speed control.
- Each motor has integral thermal overload protection.
- Fans are suitable for operating temperatures between -200C and +700C fixed speed and -200C and +500C speed controlled.
- Impellers Adjustable pitch aerofoil impellers are providing with blades made from high quality pressure die cast aluminium (LM6) natural finish with the hubs manufactured from die cast aluminium alloy (LM24).
- Impellers are factory set at an angle to provide maximum performance.
- Assembled impellers are to be dynamically balanced to Grade G6.3.
|
Testing
|
- The SCPP has been introduced to satisfy the requirements of DW172.
- Units are to be designed and manufactured with procedures as defined in BS EN ISO 9001: 2000.
- All SCPP units are to be tested to ISO 5801: 1997 (airside performance) and BS 848 Part 2: 1985 (sound performance).
|
Dimensions
|
|
|
Model SCPP |
A |
B |
C |
E |
F |
G |
K |
Kg |
500/4-1 |
500 |
585 |
500 |
12 |
12 |
560 |
20 |
55 |
560/4-1 |
560 |
|
500 |
12 |
12 |
620 |
20 |
60 |
630/4-1 |
630 |
715 |
500 |
12 |
12 |
690 |
20 |
70 |
|
Performance
|
|
|
|
m3/s @ Pa |
Model SCPP |
0 |
50 |
100 |
150 |
200 |
250 |
300 |
350 |
400 |
450 |
500 |
550 |
600 |
500/4-1 |
2.37 |
2.3 |
2.24 |
2.17 |
2.09 |
2.01 |
1.91 |
1.77 |
1.64 |
|
|
|
|
560/4-1 |
3.19 |
3.11 |
3.01 |
2.91 |
2.8 |
2.67 |
2.51 |
2.32 |
2.05 |
1.69 |
1.3 |
1.02 |
|
630/4-1 |
4.29 |
4.18 |
406 |
3.94 |
3.81 |
3.66 |
3.49 |
3.28 |
3.05 |
2.68 |
2.3 |
1.89 |
1.45 |
|
Technical Data
|
Model SCPP |
r.p.m. |
FLC Amps |
SC Amps |
Output kW |
500/4-1 |
1350 |
72 |
21.6 |
1.1 |
560/4-1 |
1350 |
9.8 |
30 |
1.5 |
630/4-1 |
1350 |
15.8 |
39.6 |
2.2 |
|
Sound Data
|
|
|
Octave Band Hz |
Octave Band kHz dB(A) |
Model SCPP |
|
63 |
125 |
250 |
500 |
1 |
2 |
4 |
8 |
@ 3m |
500/4-1 |
Inlet |
75 |
75 |
82 |
80 |
78 |
75 |
70 |
63 |
62 |
Outlet |
76 |
76 |
82 |
79 |
79 |
77 |
73 |
67 |
63 |
560/4-1 |
Inlet |
80 |
79 |
84 |
83 |
82 |
80 |
76 |
69 |
66 |
Outlet |
82 |
80 |
84 |
84 |
83 |
82 |
79 |
72 |
68 |
630/4-1 |
Inlet |
83 |
83 |
87 |
88 |
85 |
83 |
79 |
73 |
70 |
Outlet |
85 |
83 |
87 |
88 |
86 |
86 |
82 |
77 |
71 |
|
Auto Cad
|
SCPP 500 4 -1 |
SCPP 560 4 -1 |
SCPP 630 4 -1 |
PDF
|
|
|
|
|
|
|
|
|